-Multi-stage protection with primary or combination primary/secondary protectors -10 pair protector -Provides both L-L and L-PE protection modes for comprehensive protection -Simple installation into Krone® LSA disconnect block -Data Line Terminator (DLT) available where screw terminal connections are requiredPart Number HSP10K230 Article Number 700860 Max Continuous Operating Voltage (Uc) 190 VDC Max Discharge Current (Imax), L+L-PE 20 kA 8/20 μs Rated Load Current (IL) 150 mA Frequency 12 MHz Max Transmission Rate 8 Mb/s Protection Modes L-L L-PE Technology Multi-stage Connection Type Krone® LSA-PLUS Impedance Balance 55 dB Max Insertion Loss .4 Db Max Return Loss 20 dB Max Loop Resistance 6.6 Ω Temperature -20 to 60 °C Enclosure Material UL® 94V-0 Thermoplastic Depth (D) 21 mm Height (H) 35 mm Width (W) 125 mm Unit Weight 0.02 kg Certification Details UL® 497 Certifications A-Tick (Australia) CE C-Tick cULus Qualifoudre Standard Packaging Quantity 1 pc UPC 78285647505 EAN-13 9321098000545